Dwelling Unit Calculations (2024)

The calculation is pretty simple.

2,000 sq ft x 3VA = 6,000VA.

No additional load is required for general-use receptacles and lighting outlets because they are included in the 3VA per sq ft load specified by Table 220.12 for dwelling units. See 220.14(J).

Now let’s work through an example to determine the number of circuits required.

Question: How many 15A circuits are required for a 2,000-sq-ft dwelling unit?

Step 1: General lighting VA = 2,000 sq ft x 3VA = 6,000VA

Step 2: General lighting amperes:
I = VA ÷ E
I = 6,000VA ÷ 120V*
I = 50A
*Use 120V, single-phase unless specified otherwise.

Step 3: Determine the number of circuits:
Number of circuits = General lighting amperes ÷ circuit amperes
Number of circuits = 50A ÷ 15A
Number of circuits = 3.30, or 4 circuits. Any fraction of a circuit must be rounded up.

Optional method for feeder and service load calculations

You can use the optional method [Art. 220, Part IV] only for dwelling units served by a single 120/240V or 120/208V 3-wire set of service or feeder conductors with an ampacity of 100A or larger [220.82]. The optional method consists of three calculation steps:

  1. General loads [220.82(B)]
  2. Heating and air-conditioning load [220.82(C)]
  3. Feeder/service conductors [310.15(B)(6)]

Step 1: General loads [220.82(B)]

The general calculated load must be at least 100% for the first 10kVA, plus 40% of the remainder of the following loads:

  1. General lighting and receptacles: 3VA per sq ft
  2. Small-appliance and laundry branch circuits: 1,500VA for each 20A, 120V small-appliance and laundry branch circuit specified in 220.52.
  3. Appliances: The nameplate VA rating of all appliances and motors that are fastened in place (permanently connected) or located on a specific circuit, not including heating or air-conditioning.

Be sure to calculate the range and dryer at their nameplate ratings.

Step 2: Heating and air-conditioning load [220.82(C)]

Include the larger of (1) through (6):

  1. Air-conditioning equipment: 100%
  2. Heat-pump compressor without supplemental heating: 100%
  3. Heat-pump compressor and supplemental heating: 100% of the nameplate rating of the heat-pump compressor and 65% of the supplemental electric heating for central electric space-heating systems. If the control circuit is designed so that the heat-pump compressor can’t run at the same time as the supplementary heat, omit the compressor from the calculation.
  4. Space-heating units (three or fewer separately controlled units): 65%.
  5. Space-heating units (four or more separately controlled units): 40%.
  6. Thermal storage heating: 100%.

Step 3: Feeder/service conductors [310.15(B)(6)]

  • 400A and less. For individual dwelling units of one-family, two-family, and multi-family dwellings, use Table 310.15(B)(6) to size 3-wire, single-phase, 120/240V service or feeder conductors (including neutral conductors) that serve as the main power feeder. Feeder conductors aren’t required to have an ampacity rating greater than the service conductors [215.2(A)(3)]. Size the neutral conductor to carry the unbalanced load per Table 310.15(B)(6). Table 310.15(B)(6) can’t be used for sizing the feeder or service conductors that supply more than a single dwelling unit.
  • Over 400A. Size ungrounded conductors and the neutral conductor using Table 310.16 for feeder/services over 400A and those that do not fill all of the requirements for using Table 310.15(B)(6). Let’s try a calculation example.

Question: What size service conductor is required for a 1,500-sq-ft dwelling unit containing the following loads?
Cooktop: 6,000VA
Disposal: 900VA
Dishwasher: 1,200VA
Dryer: 4,000VA
Ovens (two each): 3,000VA
Water heater: 4,500VA
A/C: 17A, 230V
Electric heating (one control unit): 10kVA

Step 1: General loads [220.82(B)]
General lighting: 1,500 sq ft x 3VA = 4,500VA
Small-appliance circuits: 1,500VA x 2 circuits = 3,000VA
Laundry circuit: 1,500VA
Appliances (nameplate):
Cooktop: 6,000VA
Disposal: 900VA
Dishwasher: 1,200VA
Dryer: 4,000VA
Ovens (each 3 kW): 6,000VA
Water heater: 4,500VA

Total connected load: 31,600VA

First 10kW at 100%: 10,000VA x 1.00 = 10,000VA

Remainder at 40%: 21,600VA x 0.40 = 8,640VA

Calculated general load: 10,000VA + 8,640VA

Calculated general load: 18,640VA

Step 2: Air-Conditioning versus heat [220.82(C)]

Air-conditioning at 100% [220.82(C)(1)] vs. electric space heating at 65% [220.82(C)(4)]

Air conditioner [Table 430.248]:
A/C VA = V x A
A/C VA = 230V x 17A
A/C VA = 3,910VA (omit)

Electric space heat: 10,000VA x 0.65 = 6,500VA

Step 3: Feeder/service conductors [310.15(B)(6)]

Calculated general load (Step 1): 18,640VA

Heat calculated load (Step 2): 6,500VA

Total calculated load = 18,640VA + 6,500VA = 25,140VA

I = VA ÷ E

I = 25,140VA ÷ 240V = 105A

Therefore, the feeder/service ungrounded conductor is sized to 110A, 3 AWG [310.15(B)(6)].

The NECdoesn’t explain how demand factors were derived, and it’s not essential that you understand this in order to apply them correctly. Be sure to work on some practice calculations so you understand how to apply the various demand factors to a dwelling unit calculation.

The standard calculation and the optional calculation methods were both discussed in this article. These are two distinctly different calculation methods, so be careful not to mix them. Remember that the standard method is in Part III of Art. 220, and the optional method is contained in Part IV. When you are evaluating the necessary loads in either type of calculation method, follow the requirements for specific loads covered in other Articles outside of Art. 220. Which method is better to use? On an exam, you’ll likely be told which method to use on a specific question. However, if the question doesn’t specify a method, use the standard calculation. The optional method is usually faster and easier to apply, so it has a natural advantage for daily use on the job.

SIDEBAR: Where to Find Dwelling Unit Code Requirements Outside Art. 220

Branch circuits — Art. 210

Areas supplied by small appliance circuits — 210.52(B)(1)

Feeders — Art. 215

Services — Art. 230

Overcurrent protection — Art. 240

Wiring methods — Art. 300

Conductors — Art. 310

Appliances — Art. 422

Electric space-heating equipment — Art. 424

Motors — Art. 430

Air-conditioning equipment — Art. 440

For more information, read "Load Calculations -- Part 1."

Dwelling Unit Calculations (2024)

FAQs

How do you calculate equivalent dwelling units? ›

Equivalent dwelling unit (EDU means the quotient of “Q” divided by 350 gallons per day, where Q is equal to the estimated average daily flow of sewage from the connected occupied building being considered.

How many 15A circuits are required for a 2000 sq ft dwelling unit? ›

According to the NEC, a 2000 square foot house would require a minimum of four (c) branch circuits if 15 amp circuits are used. Each branch circuit can accommodate multiple electrical outlets, and the number of required circuits is determined based on the load calculations and electrical requirements of the house.

What is the unit load per square foot for a dwelling? ›

In one-family, two-family, and multifamily dwellings, the minimum unit load shall be not less than 33 volt-amperes/m2 (3 volt-amperes/ft2).

What is the NEC code for dwelling units? ›

NEC Article 230.67 definition of dwelling unit includes your home. Per the National Electric Code (NEC 2020), a dwelling unit is a single unit, providing complete and independent living facilities for one or more persons, including permanent provisions for living, sleeping, cooking and sanitation.

What is 4 dwelling units? ›

Four-unit dwelling or "fourplex" means a building designed for four attached dwelling units in which the dwelling units share a common separation, such as a ceiling or wall, and in which access cannot be gained between the units through an internal doorway, excluding common hallways.

How is ADU square footage calculated? ›

For attached ADUs, the square footage can never be more than 50% that of the main residence. For detached ADUs, if the planned size exceeds that of the primary dwelling, the ADU size is limited to a maximum of 800 square feet. This is one example of the complexity of the laws around how big an ADU can be in California.

How many 20 amp circuits are required in a dwelling unit? ›

To find the minimum number of 20-amperes, 2-wire circuits for lighting and general-use receptacles, divide 48 by 20 (48 ÷ 20 = 2.4 = 3). The minimum number of 20-ampere, 2-wire general-purpose branch circuits for lighting and receptacles in this dwelling is three.

How do you calculate single dwelling load? ›

Single Dwelling Unit Calculation

Multiply the total square footage of the unit as measured from the exterior walls by 3VA per square foot. This factor includes all the general purpose receptacles and lighting fixtures.

How many 15A 120V general purpose circuits are required for a 2000 sq ft dwelling unit? ›

Question: How many 15A circuits are required for a 2,000-sq-ft dwelling unit? *Use 120V, single-phase unless specified otherwise. Number of circuits = 3.30, or 4 circuits.

How do you calculate residential loads? ›

Add together the wattage capacity of all general lighting branch circuits. Add in the wattage rating of all plug-in outlet circuits. Add in the wattage rating of all permanent appliances (ranges, dryers, water heaters, etc.) Subtract 10,000.

How do I calculate the load of my house? ›

Add up the watt ratings of all the fixtures and appliances that will be using power simultaneously. Add in the watt rating of every plug-in outlet. Add in the watt of every permanent appliance like dryer/washer, water heater, etc. Add 10000.

What is a dwelling unit in construction? ›

August 2022. A housing unit, or dwelling unit, (at later mention often abbreviated to unit) is a structure or the part of a structure or the space that is used as a home, residence, or sleeping place by one person or more people who maintain a common household.

How many outdoor receptacles are required for a dwelling unit? ›

Specific exceptions may be made for snow-melting or deicing equipment, where the equipment is powered by an inaccessible outlet. The required GFCI protection can be provided by GFCI receptacles or GFCI circuit breakers. Homes must have at least one outdoor receptacle at the front and rear of the house.

What location in a dwelling unit requires GFCI protection? ›

GFCI protection shall be provided for all 125-volt through 250 volt, receptacle outlets installed outdoors, indoor damp and wet locations, in boathouses, crawl spaces, basem*nts, laundry areas, garages, accessory buildings, bathrooms, at kitchen countertops and within 6-feet of the top inside edge of all sink bowls, ...

Which of the following locations at dwelling units require GFCI? ›

GFCI receptacles are required in bathrooms, garages, crawl spaces, basem*nts, laundry rooms and areas where a water source is present.

How do you calculate equivalent cost per unit? ›

To calculate cost per equivalent unit by taking the total costs (both beginning work in process and costs added this period) and divide by the total equivalent units. In this example, beginning work in process is zero.

How do you calculate equivalent units of labor? ›

We can make this calculation easier by multiplying the units by a percentage of complete. For example, if we bring 1,000 units to a 40 % state of completion, this is equivalent to 400 units (1,000 x 40%) that are 100% complete.

How are equivalent units calculated on the basis of wages? ›

Formula for Equivalent Units of Production

For example, the closing stock of 200 units in a process, with 60% complete in respect of materials, wages, and overheads, is equivalent to 120 units (i.e., 200 x 60%), which are 100% complete.

How do you compute the equivalent units for materials and conversion costs? ›

The equivalent units are calculated by multiplying the number of units by the percentage of completion for each stage of the production process. Percent complete in ending work in process: 100% (for materials) and 60% (for conversion).

Top Articles
Latest Posts
Article information

Author: Madonna Wisozk

Last Updated:

Views: 6253

Rating: 4.8 / 5 (48 voted)

Reviews: 95% of readers found this page helpful

Author information

Name: Madonna Wisozk

Birthday: 2001-02-23

Address: 656 Gerhold Summit, Sidneyberg, FL 78179-2512

Phone: +6742282696652

Job: Customer Banking Liaison

Hobby: Flower arranging, Yo-yoing, Tai chi, Rowing, Macrame, Urban exploration, Knife making

Introduction: My name is Madonna Wisozk, I am a attractive, healthy, thoughtful, faithful, open, vivacious, zany person who loves writing and wants to share my knowledge and understanding with you.